Quick answer
IPC/WHMA-A-620 is the acceptance standard for cable and wire harness assemblies. It grades workmanship in three classes: Class 1 (general products), Class 2 (dedicated service, the usual default for industrial and automotive work) and Class 3 (high performance). The customer chooses the class. The current revision is F, dated October 2025 in IPC's document revision table (checked 2026-11-26); the revision named on your drawing is the one that applies to your build.
If you've ever received a spec sheet requiring "IPC Class 2" or "IPC/WHMA-A-620 Class 3," or wondered what makes a high-reliability industrial harness different from a consumer product, you've encountered IPC/WHMA-A-620—often shortened to IPC 620. This standard, formally titled "Requirements and Acceptance for Cable and Wire Harness Assemblies," is the global benchmark for wire harness quality.
This guide is written for buyers and quality engineers who need to specify, source, or verify IPC/WHMA-A-620 compliant wire harnesses without wading through the full standard. We cover what each class actually requires, the specific crimp, solder, splice, and marking criteria inspectors use, which revision is current (Revision F, October 2025) and when each earlier revision was released, how A-620 relates to IPC-A-610 and J-STD-001, and exactly how to confirm a supplier really builds to it. The class tables below are a plain-language summary of how the classes differ; the purchased standard, your drawing, and your contract set the actual acceptance limits.
What is IPC/WHMA-A-620?
IPC/WHMA-A-620 is a joint standard developed by IPC (Association Connecting Electronics Industries) and WHMA (Wire Harness Manufacturers Association). First published in January 2002 and revised six times since (Revision F, October 2025, is the current one), it provides visual and measurable criteria for evaluating the quality of a cable harness. It is the harness-assembly counterpart to the broader family of IPC electronics standards. If your program requires it, see how we document IPC/WHMA-A-620 conformance at our facility.
A-620 Covers:
Wire Preparation
Cutting, stripping, tinning requirements
Crimping
Terminal crimps, splice crimps, insulation crimps
Soldering
Hand soldering, pot tinning, heat shrink
Assembly
Connector assembly, lacing, bundling, labeling
Protection
Sleeving, molding, potting, strain relief
Testing
Electrical test requirements and documentation
The standard defines three product classes, each with progressively stricter requirements. The customer decides which class applies and states it on the drawing, purchase order, or contract; the manufacturer builds and inspects to it. If no class is stated, agree on one in writing before first article. That choice drives every quality decision from design through inspection.
Current Revision: IPC/WHMA-A-620F and Revision History
The current revision is IPC/WHMA-A-620F, listed as "Rev F 10/25" in IPC's document revision table. A common source of confusion in RFQs is the revision letter: each revision updates the acceptance criteria, so an "IPC/WHMA-A-620 Class 3" callout can mean different limits under revision B than under revision F. The letter defines which acceptance limits your inspector will actually apply.
IPC/WHMA-A-620 Revision Dates and Gaps Between Revisions
| Revision | Date in IPC Table | Months Since Previous Revision (our calculation) | Space Addendum in IPC Table |
|---|---|---|---|
| Original | 1/02 (January 2002) | — | — |
| A | 7/06 (July 2006) | 54 | A-S 1/11; Amendment 1 7/12 |
| B | 10/12 (October 2012); Amendment 1 8/13 | 75 | B-S 6/13 |
| C | 1/17 (January 2017) | 51 | C-S 4/18 |
| D | 1/20 (January 2020) | 36 | D-S 9/20 |
| E | 10/22 (October 2022) | 33 | E-S 10/23 |
| F (current) | 10/25 (October 2025) | 36 | None listed as of 2026-11-26 |
Source: IPC document revision table (ipc.org), IPC/WHMA-A-620 rows, read on 2026-11-26. The table gives month and year only. The gap column is our calculation: whole months from one base revision's month to the next (for example 7/06 to 10/12 = 75 months). Amendments and addenda are not counted as revisions. By our count the gaps range from 33 to 75 months, and each of the last three was about three years.
What the Revision History Means for Buyers
- A new revision does not change an existing contract. If your print says "IPC/WHMA-A-620B," the harness is built and inspected to that edition until the drawing is revised.
- Legacy drawings are common. Revisions B through E are still cited on released drawings, so a supplier should be able to tell you which editions its operators are trained to.
- Addenda are separate documents. The IPC table lists space-application addenda (the "-S" documents above) and a rail-application addendum (CR, 3/22). They apply only when the contract names them.
- The design companion is IPC-D-620. A-620 is an acceptance standard for the built harness; design guidance sits in IPC-D-620 (Revision A, 12/21 in the same IPC table).
Buyer tip: pin the revision before first article
Write the full callout on your drawing or purchase order—for example "IPC/WHMA-A-620F, Class 2"—rather than a bare "IPC 620." If the revision is left open, agree on it with your supplier before first-article inspection so acceptance limits aren't disputed after parts are built.
Class 1 vs Class 2 vs Class 3: Which Do You Need?
The three classes aren't about "good, better, best"—they're about matching quality requirements to product end-use. Applying Class 3 criteria to a Class 1 product wastes money; applying Class 1 criteria to a Class 3 product invites failure.
| Aspect | Class 1 | Class 2 | Class 3 |
|---|---|---|---|
| Description | General Electronic Products | Dedicated Service Products | High Performance Products |
| Typical Applications | Consumer electronics, toys, appliances | Industrial, automotive, commercial | High-reliability industrial equipment, medical-equipment components |
| Failure Consequence | Inconvenience | Equipment damage, downtime | Safety critical, life-threatening |
| Typical Inspection Level (set by contract) | Per quality plan | Per quality plan | Often 100% by customer requirement |
| Documentation | Basic | Detailed | Complete traceability |
| Cost Impact | Baseline | Higher than Class 1 | Highest; quote-specific |
Class 3 is sometimes requested because it sounds like the highest quality. For a product such as a commercial HVAC controller, Class 2 is usually the appropriate level and Class 3 adds inspection cost. Match the class to the application.
The class names and descriptions follow the standard. The application, inspection, documentation, and cost rows are a general guide: the standard does not set prices or sampling plans, and those are agreed in the contract and quote.
Key Inspection Criteria
For each criterion, A-620 sorts what the inspector sees into conditions: Acceptable (meets requirements), Process Indicator (not a defect, but a sign the process needs attention) and Defect (reject). Editions through Revision C also pictured a Target condition; IPC training providers report that it was dropped from Revision D onward (reported by them, not checked by us against the paid text). The strictness increases from Class 1 to Class 3—what's acceptable in Class 1 might be a defect in Class 3.
Simplified summary. The tables in this guide show the direction of the requirements by class in plain English. They are not a copy of the standard and must not be used as acceptance limits. IPC/WHMA-A-620 is a paid, copyrighted document; the numeric limits are in the revision named on your drawing.
Wire Stripping Criteria
| Criteria | Class 1 | Class 2 | Class 3 |
|---|---|---|---|
| Nicked strands | Limited number allowed | Fewer allowed | Tightest limit |
| Severed strands | Limited number allowed | Fewer allowed | Tightest limit |
| Insulation damage | Minor acceptable | No exposed conductor | Pristine required |
The standard sets strand damage limits by the number of strands in the conductor and by class; check its strand damage table for the count that applies to your wire.
Connector Pin/Socket Criteria
| Criteria | Class 1 | Class 2 | Class 3 |
|---|---|---|---|
| Terminal seating | Functional | Fully seated and locked | Fully seated and locked; tightest limits |
| Pin damage | Cosmetic flaws tolerated if function is unaffected | No functional impact | Least damage tolerated |
| Retention force | Per connector spec | Per connector spec | Per connector spec; test level set by contract |
Crimping Requirements by Class
Crimping is where A-620 gets very specific. The standard defines measurable criteria for crimp height, bellmouth, conductor visibility, and insulation support. These are the features an inspector checks on a crimp. The dimensional limits themselves come from the terminal manufacturer's specification and the purchased standard, so the table below describes the direction of each requirement rather than quoting limits.
| Crimp Attribute | Class 1 & 2 | Class 3 |
|---|---|---|
| Crimp Height | Within manufacturer spec | Within the terminal manufacturer's crimp height specification, with tighter process control |
| Bellmouth (Front) | Visible, protects strands | Required, measurable per spec |
| Conductor Visibility | Strands visible in inspection window | Full conductor engagement verified |
| Insulation Crimp | Grips insulation, no conductor damage | Defined gap from conductor crimp |
| Pull Force Testing | Sampling plan set by the quality plan or contract | Plan set by the contract; high-reliability programs commonly add setup and in-process samples |
Critical: Crimp Cross-Section Analysis
High-reliability programs often call for cross-section analysis of crimps to check conductor compression and voids. It is a destructive test, so it is run on samples: it shows that a given terminal, wire, and tooling setup produces a sound crimp, not that every part in the lot was tested. Whether it is required, and how often, is set by the contract or quality plan.
For detailed crimping techniques, see our crimping best practices guide.
Soldering Standards
While crimping dominates modern harness manufacturing, soldering still applies to PCB connections, shielding terminations, and specialty applications. A-620 references IPC J-STD-001 for soldering workmanship, with acceptance limits that tighten from Class 1 to Class 3. The cards below show the direction of the difference, not the limits; inspection level and magnification are set by the standard and your quality plan.
Class 1 soldering
- Widest acceptance limits for wetting and fill
- Cosmetic imperfections tolerated when function is unaffected
- Inspection level set by the quality plan
Class 2 soldering
- Tighter limits for wetting and fill
- Fewer imperfections tolerated
- Inspection level set by the quality plan
Class 3 soldering
- Tightest limits for wetting and fill
- Fewest imperfections tolerated
- Inspection level and rework rules set by the contract and quality plan
Harness Assembly Requirements
Beyond individual connections, A-620 specifies how the complete harness should look and function. These assembly-level requirements cover wire routing, bundling, and protection.
Wire Routing & Bundling
Wires should follow natural paths without excessive tension or sharp bends. Minimum bend radius is set by wire and cable type in the standard; see our bend radius guide for the public NASA and NEC values.
Lacing & Tie Wraps
Lacing patterns must be consistent and tight. Cable ties must not cut into insulation. Whether lacing or cable ties are used is set by the drawing.
Strain Relief
Terminations need appropriate strain relief to prevent wire stress at termination points. The method (boot, overmold, backshell, or clamp) is set by the drawing.
Labeling & Marking
Wire labels must be legible, permanent, and positioned per drawing. Lot or serial traceability on labels is a contract requirement, not something the class alone adds.
Protective Covering
Sleeving, conduit, and spiral wrap must be properly secured and provide specified coverage. Required coverage is set by the drawing.
Documentation & Traceability
A-620 is an acceptance standard, so most record-keeping is set by your contract and the supplier's quality system rather than by the class itself. The table shows the pattern buyers commonly specify at each class; it is not text from the standard. Write the records you need into the purchase order.
| Record (commonly specified) | Class 1 | Class 2 | Class 3 |
|---|---|---|---|
| Inspection Records | Often not requested | Commonly requested per lot | Commonly requested per unit |
| Material Certs | On request | Commonly kept on file | Commonly lot traceable |
| Test Reports | Summary, if requested | Commonly per lot | Commonly per serial number |
| Operator Training | Per supplier quality system | Per contract | Per contract; trained inspectors commonly specified |
| Record Retention | Per contract | Per contract | Per contract; often the longest |
For a Class 3 harness, traceability should connect the finished assembly to its wire and terminal lots, operator records, and inspection results. Agree on the required records and retention period before production so future service investigations have useful evidence.
Process Control vs. Final Inspection
A-620 tells an inspector whether a finished crimp, splice, or solder joint is acceptable. It does not run the process that produced it. Crimp height checks at setup, pull tests after a tooling change, and applicator maintenance are process controls that belong in the supplier's control plan. When you qualify a supplier, ask for both: the inspection criteria (A-620 class and revision) and the control plan that keeps the process inside them.
A-620 vs IPC-A-610 vs J-STD-001
These three IPC documents are constantly mixed up in specifications, yet they judge different things. Getting the reference right on your drawing prevents a supplier from applying the wrong acceptance criteria.
| Standard | What It Governs | Use It To Judge |
|---|---|---|
| IPC/WHMA-A-620 | Cable and wire harness assembly workmanship | Crimps, splices, connectors, lacing, protection on a harness |
| IPC-A-610 | Acceptability of populated printed circuit boards | Component placement and solder joints on a PCB |
| J-STD-001 | Soldered electrical and electronic assemblies (process requirements) | The soldering process itself, referenced by both A-620 and A-610 |
In short: use A-620 to accept a harness, IPC-A-610 to accept a circuit board, and J-STD-001 for the underlying solder process. All three share the same Class 1/2/3 model, so a "Class 3" program is consistent across them. For a broader look at how these sit alongside product and management-system certifications, see our roundup of the top wire harness certifications and how UL vs CSA vs CE marks differ from workmanship standards.
How to Verify a Supplier Builds A-620 Compliant Wire Harnesses
"We build to IPC/WHMA-A-620" is easy to write on a website. Because A-620 defines workmanship you build to—not a company-wide accreditation like ISO 9001—the burden is on the buyer to confirm it's real. Here's the evidence a genuine A-620 shop can produce on request:
Current CIS / CIT certificates
Ask for Certified IPC Specialist (CIS) or Certified IPC Trainer (CIT) certificates for the operators and inspectors on your job—and check they are still within their validity window.
The specific revision and class
A compliant supplier states exactly what they build to (e.g. "A-620F, Class 2") rather than a vague "IPC compliant." Vagueness here is a red flag.
First-article & crimp cross-section reports
Request a sample first-article inspection report and, for Class 3, crimp cross-section (micro-section) analysis showing proper conductor compression and void-free termination.
Traceability records
For Class 2/3, the shop should show lot traceability linking wire spool, terminal lot, and operator to a finished harness serial number.
A documented quality system behind it
A-620 workmanship lives inside a quality system. Confirm how it is controlled on the floor—our own approach is described on our quality capabilities page.
Want to go deeper on supplier audits? See how we run quality control and inspection, the certifications we hold and follow, and a worked example of an A-620–built JST connector assembly.
Common Misconceptions About IPC 620
Myth: "Class 3 always means better quality."
Reality: Class 3 means tighter acceptance limits for high-performance, safety-critical products, with more inspection and documentation cost. For most commercial and industrial harnesses, Class 2 is the correct, more economical target. Higher class ≠ better value.
Myth: "A-620 certifies the company."
Reality: A-620 certifies people (CIS/CIT) and defines how work is accepted. There is no company-wide 'A-620 certified' stamp the way ISO 9001 or IATF 16949 accredit an organization. Judge the operators and the evidence, not a logo.
Myth: "IPC 620 and IPC 610 are interchangeable."
Reality: They are separate standards—A-620 for harnesses, A-610 for circuit boards. Citing the wrong one on a drawing can send your harness to the wrong acceptance criteria.
Myth: "The revision letter doesn't matter."
Reality: It does. Acceptance limits can shift between revisions (B, C, D, E and the current F). A bare 'IPC 620' with no revision or class is an incomplete spec that invites disputes at inspection.
Myth: "Once a crimp looks fine, it passes."
Reality: Visual acceptance is only part of it. A-620—especially Class 3—backs the visual criteria with pull-force testing and crimp cross-section analysis to catch problems the eye can't see.
Getting IPC/WHMA-A-620 Certified
Under IPC's A-620 training and certification program, the credential belongs to an individual, not to a factory or a production line. A CIS or CIT certificate carries a two-year validity and names the revision the person was trained on, so ask which revision appears on it. Program rules change, so confirm current policy with IPC or a licensed training center. The two credentials buyers see most often are:
CIS - Certified IPC Specialist
Operators and inspectors who apply A-620 criteria daily. Training covers visual inspection, measurement techniques, and acceptance decisions.
- Course length varies by training center
- Exam format set by the IPC program
- 2-year certification validity
CIT - Certified IPC Trainer
Trainers who are certified to teach the A-620 course and certify CIS candidates, often in-house at larger manufacturers.
- Delivered by IPC-licensed training centers
- Exam format set by the IPC program
- Can train and certify CIS candidates
View our certifications page to see the personal IPC/WHMA-A-620 CIS and IPC-A-610 CIS credentials held by one quality specialist at Hebei Cloom, alongside its quality-system certifications.
Sources & Data As Of
- IPC document revision table: revision letters and dates for IPC/WHMA-A-620, its space and rail addenda, and IPC-D-620. Read on 2026-11-26.
- Gaps between revisions are our own calculation from the dates in source 1 (whole months, base revisions only).
- The removal of the Target condition from Revision D onward is reported by IPC training providers; we did not check it against the paid standard.
- The criteria tables are a plain-English summary and do not reproduce the standard. We did not read the text of Revision F for this update; numeric acceptance limits must be taken from the revision named on your drawing.
- Personnel credentials at Hebei Cloom are described on our certifications page.
Frequently Asked Questions
What is IPC/WHMA-A-620 (IPC 620)?
IPC/WHMA-A-620, often shortened to IPC 620, is the joint IPC and WHMA standard titled "Requirements and Acceptance for Cable and Wire Harness Assemblies." It defines acceptable, process indicator, and defect conditions for wire preparation, crimping, soldering, connectorization, and protection of cable and wire harness assemblies, graded by three product classes.
What is the current revision of IPC/WHMA-A-620?
Revision F, dated 10/25 (October 2025) in IPC's document revision table, checked on 2026-11-26. It replaced Revision E (10/22). A newer revision does not automatically change an existing contract: the revision named on the drawing or purchase order is the one the harness is built and inspected to.
What is the difference between Class 1, Class 2, and Class 3?
Class 1 (General Electronic Products) prioritizes function for consumer-grade items. Class 2 (Dedicated Service Products) adds reliability for industrial, automotive, and commercial equipment and is the most common default. Class 3 (High Performance Products) addresses products where continued performance is critical. For industrial controls or medical-equipment cable components, specify the class and inspection requirements according to the application and customer agreement.
Who decides which IPC/WHMA-A-620 class applies?
The customer (the user of the harness) does. The class is stated on the drawing, purchase order, or contract, and the manufacturer builds and inspects to it. If no class is stated, agree on it in writing before first article instead of letting the supplier assume one.
What does IPC/WHMA-A-620 Class 3 require?
Class 3 applies the tightest acceptance limits in the standard to wire preparation, crimps, solder joints, connector assembly, and harness protection. The exact limits are in the revision named on your drawing. Inspection sampling, rework rules, traceability, and record retention are usually set by the customer contract and the quality plan, not by the class alone.
What's the difference between IPC/WHMA-A-620 and IPC-A-610?
IPC-A-610 covers acceptability of electronic assemblies (populated printed circuit boards), while IPC/WHMA-A-620 covers cable and wire harness assemblies. They share the same three-class model, but you use A-620 to judge a harness and A-610 to judge a PCB. Soldering workmanship in both points to IPC J-STD-001.
What changed between IPC/WHMA-A-620 revisions?
Each revision updates the acceptance criteria, so the same class callout can mean different limits under different revision letters. IPC's document revision table lists the base revisions as original 1/02, A 7/06, B 10/12, C 1/17, D 1/20, E 10/22 and F 10/25. By our count that is 33 to 75 months between revisions, and about three years for each of the last three. State the revision on the drawing or purchase order (for example "IPC/WHMA-A-620F, Class 2"), and confirm it before first article if it is missing.
How do I verify a supplier builds IPC/WHMA-A-620 compliant wire harnesses?
Ask for current Certified IPC Specialist (CIS) or Certified IPC Trainer (CIT) certificates for the operators and inspectors on your job, the specific revision and class they build to, sample first-article inspection and crimp cross-section reports, and their traceability records. A genuine A-620 shop can show these on request. Note that A-620 defines workmanship you build to. It is not a company-wide accreditation like ISO 9001 or IATF 16949.
Is IPC/WHMA-A-620 certification mandatory?
No, A-620 is a voluntary consensus standard. However, many customers, especially in automotive, industrial, and medical-equipment programs, require it contractually, so building and inspecting to it is effectively mandatory to compete in those markets.
Related Resources
About the Author
Hommer Zhao · Founder & General Manager. About us · LinkedIn
Connect with our engineering team